IND060Industrial

Replacement of an air-conditioning generator by an electric heat pump

Replacement of the heating/cooling generation system for air conditioning of industrial buildings by a high-efficiency electric heat pump.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator IND060

Try the calculation without signing up. Results are not saved.

IND060Industrial

Replacement of an air-conditioning generator by an electric heat pump

Replacement of the heating/cooling generation system for air conditioning of industrial buildings by a high-efficiency electric heat pump.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Annual heating demandkWh/añoAnnual heating thermal demand of the industrial building.
Annual cooling demandkWh/añoAnnual cooling thermal demand of the industrial building.
Old generator efficiency%Seasonal efficiency of the existing heating generator.
EER of the old cooling equipment-Energy efficiency ratio of the existing cooling equipment.
Heat pump SCOP-Seasonal coefficient of performance in heating mode.
Heat pump SEER-Seasonal energy efficiency ratio in cooling mode.

Contexto e importancia de la bomba de calor para climatizacion industrial

La climatizacion de espacios industriales, almacenes, naves de producción y oficinas anexas representa un consumo energético considerable, especialmente en zonas climaticas con veranos calurosos e inviernos frios. Muchas instalaciones industriales españolas utilizan generadores de calor (calderas de gas) para calefaccion y equipos de expansion directa o enfriadoras de agua para refrigeracion, configurando sistemas separados con rendimientos que no se benefician de las sinergias posibles entre ambas demandas.

La ficha IND060 certifica el ahorro obtenido al sustituir estos generadores de climatizacion por bombas de calor electricas reversibles de alta eficiencia, capaces de cubrir simultaneamente las demandas de calefaccion y refrigeracion con un único equipo y un rendimiento estacional (SCOP/SEER) muy superior.

Fundamento técnico de la bomba de calor en climatizacion

Las bombas de calor electricas aerotermicas o geotermicas aprovechan la energía del entorno (aire, agua o suelo) para producir calor o frio según la estacion. En modo calefaccion, el SCOP (Seasonal Coefficient of Performance) mide el rendimiento estacional, reflejando la eficiencia media a lo largo de toda la temporada de calefaccion considerando variaciones de temperatura exterior. En modo refrigeracion, el SEER (Seasonal Energy Efficiency Ratio) mide analogamente el rendimiento estacional en refrigeracion.

Frente a una caldera de gas con rendimiento del 85-92% y una enfriadora con EER de 2,5-3,0, una bomba de calor moderna puede alcanzar SCOP de 3,5 a 5,0 y SEER de 4,0 a 6,5, dependiendo de la tecnología y las condiciones climaticas. Esta ventaja se amplifica con tecnologías como la compresion con inverter, los intercambiadores de microcanales y la gestión inteligente de la carga termica.

Calculo del ahorro y ejemplo práctico

Ejemplo numerico

  • Demanda calefaccion: 180.000 kWh/ano
  • Demanda refrigeracion: 120.000 kWh/ano
  • Rendimiento caldera anterior: 0,88
  • EER enfriadora anterior: 2,7
  • SCOP bomba de calor: 4,0
  • SEER bomba de calor: 5,2
Consumo calefaccion antes = 180.000 / 0,88 = 204.545 kWh/ano (gas)
Consumo refrigeracion antes = 120.000 / 2,7 = 44.444 kWh/ano (elect.)
Consumo calefaccion después = 180.000 / 4,0 = 45.000 kWh/ano (elect.)
Consumo refrigeracion después = 120.000 / 5,2 = 23.077 kWh/ano (elect.)

El ahorro debe calcularse en terminos de energía final, considerando la conversion de gas a kWh PCS cuando corresponda. El ahorro total en energía final puede superar los 150.000 kWh/ano en este tipo de instalación.

CAE total = 150 MWh
Valor estimado = 150 MWh x 100 EUR/MWh = 15.000 EUR

Errores frecuentes en la preparacion del expediente CAE

  • Mezclar demandas de calefaccion y refrigeracion: Cada demanda debe calcularse por separado con su rendimiento correspondiente.
  • No utilizar rendimientos estacionales: La ficha requiere SCOP y SEER, no COP y EER puntuales. Los valores estacionales se obtienen según la norma UNE-EN 14825.
  • No documentar la demanda termica real: Se debe justificar la demanda con calculos de carga termica, facturas energéticas historicas o mediciones.
  • Ignorar la conversion entre energía electrica y gas: Al comparar sistemas que utilizan distintas fuentes de energía, la conversion debe hacerse de forma coherente y documentada.

Marco normativo aplicable

La ficha IND060 se rige por el Real Decreto 36/2023 y la Orden TED/845/2023. Las bombas de calor deben cumplir el Reglamento de ecodiseno (Reglamento UE 813/2013 y 2016/2281), el RITE y las normas de ensayo UNE-EN 14511 y UNE-EN 14825. La verificación ENAC presta especial atención a la coherencia entre los rendimientos estacionales declarados y las condiciones climaticas de la ubicacion de la instalación.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)