RES060Residential

Replacement of a combustion boiler with a heat pump

Replacement of a combustion boiler with a heat pump for the production of heating and/or domestic hot water in residential buildings.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator RES060

Try the calculation without signing up. Results are not saved.

RES060Residential

Replacement of a combustion boiler with a heat pump

Replacement of a combustion boiler with a heat pump for the production of heating and/or domestic hot water in residential buildings.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building (kWh/year).
DHW demandkWh/anoAnnual domestic hot water demand (kWh/year).
Boiler efficiency%Seasonal efficiency of the existing boiler (%).
Heat pump SCOP-Seasonal coefficient of performance of the heat pump (SCOP).

Contexto e importancia de la sustitucion de calderas por bombas de calor

La sustitucion de calderas de combustion (gas natural, gasoleo, GLP) por bombas de calor es una de las medidas de descarbonizacion mas potentes del sector residencial. La ficha RES060 del catalogo CAE reconoce el importante ahorro de energía primaria que se genera al reemplazar un sistema de calefaccion basado en combustion por uno electrico de alta eficiencia.

Las bombas de calor funcionan transfiriendo calor desde el exterior hacia el interior de la vivienda, aprovechando la energía gratuita del aire, el agua o el suelo. Por cada kWh electrico consumido, una bomba de calor moderna es capaz de aportar entre 3 y 5 kWh de calor util, lo que la convierte en la tecnología de calefaccion mas eficiente disponible actualmente.

Explicacion técnica del ahorro energético

El ahorro se produce al sustituir un equipo cuyo rendimiento máximo es del 100% (caldera de condensacion) por otro cuyo rendimiento equivalente supera el 300%. La bomba de calor no genera calor, sino que lo transfiere desde una fuente exterior (aire, agua, suelo) hacia el interior de la vivienda.

Tipos de bomba de calor

  • Aerotermia (aire-agua): la mas común, toma calor del aire exterior y lo transmite al circuito de agua
  • Aerotermia (aire-aire): equivalente a un split de climatizacion en modo calor
  • Geotermia: aprovecha la temperatura estable del subsuelo mediante sondas verticales u horizontales
  • Hidrotermia: utiliza agua subterranea o superficial como fuente de calor

El coeficiente de rendimiento (COP) de la bomba de calor mide la relación entre el calor aportado y la electricidad consumida. Un COP de 3,5 significa que por cada kWh electrico se obtienen 3,5 kWh de calor.

Ejemplo de calculo del ahorro y valoracion CAE

Sustitucion de una caldera de gas natural en una vivienda unifamiliar de Salamanca por un sistema de aerotermia aire-agua.

Datos del ejemplo

  • Demanda de calefaccion y ACS: 18.000 kWh/ano
  • Rendimiento de la caldera antigua: 90%
  • COP medio anual de la bomba de calor: 3,50
  • Factor de energía primaria electricidad: 1,954
  • Factor de energía primaria gas natural: 1,190

Calculo paso a paso

Consumo EP caldera = Demanda / Rend_caldera x FEP_gas
Consumo EP caldera = 18.000 / 0,90 x 1,190 = 23.800 kWh/ano
Consumo EP bomba calor = Demanda / COP x FEP_elec
Consumo EP bomba calor = 18.000 / 3,50 x 1,954 = 10.048 kWh/ano
Ahorro EP = 23.800 - 10.048 = 13.752 kWh/ano = 13,752 MWh/ano
CAE total = 13,752 MWh
Valoracion = 13,8 MWh x 100 EUR/MWh = 1.375 EUR

Errores comunes a evitar en la verificación ENAC

  • No considerar los factores de energía primaria: el calculo debe realizarse en energía primaria, no final
  • COP irreal: utilizar el COP medio estacional (SCOP), no el COP nominal en condiciones optimas
  • No documentar el equipo sustituido: se requiere evidencia de la caldera retirada y su rendimiento
  • No verificar la correcta instalación: dimensionamiento, carga de refrigerante y puesta en marcha deben estar documentados

Marco regulatorio aplicable

La ficha RES060 esta regulada por la Orden TED/845/2023 y el Real Decreto 36/2023. Los factores de energía primaria aplicables se definen en el documento reconocido del IDAE para la certificación energética de edificios. La eficiencia de las bombas de calor se evalua conforme al Reglamento (UE) 813/2013 de ecodiseno.

La instalación debe cumplir el RITE (Reglamento de Instalaciones Termicas en los Edificios) y ser realizada por empresa instaladora habilitada. Las entidades ENAC verificaran toda la cadena documental desde la retirada del equipo antiguo hasta la puesta en servicio del nuevo sistema.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)