RES093Residential

Hybridization in parallel mode zone D1-D3

Hybridization of a heating system in parallel mode (heat pump + boiler) for residential buildings in climatic zone D1-D3.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator RES093

Try the calculation without signing up. Results are not saved.

RES093Residential

Hybridization in parallel mode zone D1-D3

Hybridization of a heating system in parallel mode (heat pump + boiler) for residential buildings in climatic zone D1-D3.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building (kWh/year).
Boiler efficiency%Seasonal efficiency of the existing boiler (%).
Heat pump SCOP-Seasonal coefficient of performance of the heat pump (SCOP).
Heat pump coverage%Percentage of demand covered by the heat pump (%).

Contexto de la hibridacion en modo paralelo en zona climatica D1-D3

Las zonas climaticas D1, D2 y D3 corresponden a localidades del interior peninsular con inviernos frios: Burgos, Soria, Teruel, Leon, Avila, Salamanca, entre otras. La ficha RES093 permite emitir CAE por la instalación de sistemas hibridos en modo paralelo en estas zonas, donde la severidad del invierno hace que la caldera de apoyo desempene un papel mas protagonista.

La hibridacion en zonas frias presenta un equilibrio diferente al de zonas templadas. Las bajas temperaturas exteriores reducen el COP de la bomba de calor, pero esta sigue siendo mas eficiente que la caldera durante la mayor parte de las horas de calefaccion. El sistema hibrido optimiza el punto de conmutacion para maximizar el ahorro global.

Explicacion técnica del modo paralelo en zona D1-D3

En las zonas D, la temperatura de equilibrio del sistema hibrido se alcanza con frecuencia. Por debajo de esta temperatura (tipicamente entre -2 y 3 grados centigrados según el dimensionamiento), la caldera asume una fraccion creciente de la carga termica.

Caracteristicas de las zonas D1-D3

  • Grados-dia muy elevados: entre 1.800 y 2.500 K*dia/ano
  • Heladas frecuentes: numerosos dias con temperatura mínima inferior a 0 grados
  • Temporada de calefaccion extensa: de 6 a 8 meses
  • COP medio reducido: entre 2,5 y 3,2 debido a las bajas temperaturas exteriores
  • Cobertura BC menor: entre el 60% y el 75% de la demanda anual

Ejemplo de calculo del ahorro y valoracion CAE

Hibridacion en modo paralelo en un edificio de viviendas en Soria (zona D2).

Datos del ejemplo

  • Demanda calefaccion y ACS: 140.000 kWh/ano
  • Cobertura BC: 68%
  • COP medio anual: 2,90
  • Rendimiento caldera gasoleo: 88%

Calculo paso a paso

Demanda BC = 140.000 x 0,68 = 95.200 kWh/ano
Demanda caldera = 140.000 x 0,32 = 44.800 kWh/ano
Consumo EP hibrido = (95.200/2,90 x 1,954) + (44.800/0,88 x 1,190)
Consumo EP hibrido = 64.128 + 60.564 = 124.692 kWh/ano
Consumo EP solo caldera = 140.000/0,88 x 1,190 = 189.318 kWh/ano
Ahorro EP = 189.318 - 124.692 = 64.626 kWh/ano = 64,626 MWh/ano
CAE total = 64,626 MWh
Valoracion = 64,6 MWh x 100 EUR/MWh = 6.463 EUR

Errores comunes a evitar en la verificación ENAC

  • COP sobreestimado para zonas frias: no aplicar COP nominales medidos a 7 grados de temperatura exterior
  • No ajustar la cobertura a la severidad climatica: en zona D, la caldera interviene mas frecuentemente
  • Proteccion antihielo insuficiente: la bomba de calor debe estar preparada para funcionar a temperaturas muy bajas
  • Factor de energía primaria del combustible: diferenciar entre gas natural y gasoleo, que tienen factores distintos

Marco regulatorio aplicable

La ficha RES093 se regula por la Orden TED/845/2023 y el Real Decreto 36/2023. Las zonas D1-D3 se caracterizan por su alta severidad climatica de invierno según el CTE DB HE. Las bombas de calor instaladas en estas zonas deben poder operar a temperaturas exteriores de -10 grados o inferiores según la localidad.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)

Related resources

Start now

Create a file with datasheet RES093

14 days free. No card. No commitment.

Start now