RES096Residential

Hybridization alternative mode zone B3/B4

Hybridization of a heating system in alternative mode (heat pump + boiler) for residential buildings in climate zone B3/B4.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator RES096

Try the calculation without signing up. Results are not saved.

RES096Residential

Hybridization alternative mode zone B3/B4

Hybridization of a heating system in alternative mode (heat pump + boiler) for residential buildings in climate zone B3/B4.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building (kWh/year).
Boiler efficiency%Seasonal efficiency of the existing boiler (%).
Heat pump SCOP-Seasonal coefficient of performance of the heat pump (SCOP).
Heat pump coverage%Percentage of demand covered by the heat pump (%).

Contexto de la hibridacion en modo alternativo en zona climatica B3/B4

La ficha RES096 contempla los sistemas hibridos en modo alternativo instalados en las zonas climaticas B3 y B4, que corresponden a localidades con clima mediterraneo moderado como Valencia, Murcia, Sevilla o Cordoba. En estas zonas, el modo alternativo resulta una opción práctica y económica frente al modo paralelo.

El modo alternativo en zona B3/B4 ofrece un buen equilibrio entre simplicidad de la instalación y eficiencia energética. La bomba de calor opera sola durante la mayor parte de la temporada de calefaccion, y la caldera toma el relevo solo cuando las temperaturas exteriores descienden por debajo del punto de conmutacion programado.

Explicacion técnica del modo alternativo en zona B3/B4

En zona B3/B4, la temperatura de conmutacion se establece tipicamente entre 2 y 5 grados centigrados. Por encima de este umbral, la bomba de calor funciona sola con COP elevado. Por debajo, la caldera asume la totalidad de la carga.

Particularidades en zona B3/B4

  • Pocas horas por debajo del punto de conmutacion: entre 100 y 300 horas anuales según la localidad
  • COP medio BC alto: valores entre 3,5 y 4,0 gracias a las temperaturas exteriores favorables
  • Noches frias puntuales: la caldera se activa principalmente durante madrugadas de invierno
  • Demanda ACS: cubierta integramente por la bomba de calor al no haber picos de frio extremos

Ejemplo de calculo del ahorro y valoracion CAE

Hibridacion en modo alternativo en un edificio de viviendas en Murcia (zona B3).

Datos del ejemplo

  • Demanda calefaccion y ACS: 70.000 kWh/ano
  • Cobertura BC: 88%
  • COP medio BC: 3,90
  • Rendimiento caldera gas: 91%

Calculo paso a paso

Demanda BC = 70.000 x 0,88 = 61.600 kWh/ano
Demanda caldera = 70.000 x 0,12 = 8.400 kWh/ano
Consumo EP hibrido = (61.600/3,90 x 1,954) + (8.400/0,91 x 1,190)
Consumo EP hibrido = 30.854 + 10.989 = 41.843 kWh/ano
Consumo EP solo caldera = 70.000/0,91 x 1,190 = 91.538 kWh/ano
Ahorro EP = 91.538 - 41.843 = 49.695 kWh/ano = 49,695 MWh/ano
CAE total = 49,695 MWh
Valoracion = 49,7 MWh x 100 EUR/MWh = 4.970 EUR

Errores comunes a evitar en la verificación ENAC

  • No documentar la temperatura de conmutacion: parametro esencial que debe estar registrado en el sistema de control
  • Usar la ficha de modo paralelo: el modo alternativo tiene parametros y coeficientes distintos
  • Cobertura BC no ajustada a la zona: debe calcularse con datos horarios de temperatura de la localidad
  • No verificar el correcto funcionamiento del control: la conmutacion debe ser efectiva y verificable

Marco regulatorio aplicable

La ficha RES096 se encuadra en la Orden TED/845/2023 y el Real Decreto 36/2023. Los datos climaticos de referencia para las zonas B3/B4 se obtienen de las tablas del CTE DB HE. La instalación hibrida debe cumplir el RITE y la entidad ENAC comprobara la concordancia entre el modo de operación declarado y la configuración real.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)