RES099Residential

Hybridization alternative mode zone E1

Hybridization of a heating system in alternative mode (heat pump + boiler) for residential buildings in climate zone E1.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator RES099

Try the calculation without signing up. Results are not saved.

RES099Residential

Hybridization alternative mode zone E1

Hybridization of a heating system in alternative mode (heat pump + boiler) for residential buildings in climate zone E1.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building (kWh/year).
Boiler efficiency%Seasonal efficiency of the existing boiler (%).
Heat pump SCOP-Seasonal coefficient of performance of the heat pump (SCOP).
Heat pump coverage%Percentage of demand covered by the heat pump (%).

Contexto de la hibridacion en modo alternativo en zona climatica E1

La zona climatica E1, la mas fria del territorio español, plantea las condiciones mas exigentes para los sistemas hibridos. La ficha RES099 regula la emisión de CAE para sistemas hibridos en modo alternativo en esta zona, que incluye localidades como Burgos capital, Molina de Aragon y otros nucleos de alta meseta y montana.

En zona E1, el modo alternativo implica que la caldera asume una fraccion muy significativa de la demanda total, ya que las temperaturas por debajo del punto de conmutacion se registran durante muchas horas de la temporada de calefaccion. La decisión de optar por modo alternativo frente a paralelo debe estar bien fundamentada tecnicamente.

Explicacion técnica del modo alternativo en zona E1

Con temperaturas exteriores que pueden alcanzar -15 grados centigrados, la bomba de calor en modo alternativo se desactiva durante periodos prolongados. La caldera debe estar dimensionada para cubrir la totalidad de la demanda en esas condiciones.

Condiciones extremas de zona E1

  • Horas con caldera activa: entre 1.200 y 2.000 horas anuales
  • Cobertura BC limitada: entre el 45% y el 60% de la demanda anual
  • COP medio bajo: entre 2,2 y 2,7 incluso cuando la BC esta activa
  • Riesgo de heladas prolongadas: periodos de varios dias consecutivos bajo cero

Ejemplo de calculo del ahorro y valoracion CAE

Hibridacion modo alternativo en un edificio de viviendas en Reinosa (zona E1).

Datos del ejemplo

  • Demanda calefaccion y ACS: 200.000 kWh/ano
  • Cobertura BC: 52%
  • COP medio BC: 2,40
  • Rendimiento caldera gasoleo: 86%

Calculo paso a paso

Demanda BC = 200.000 x 0,52 = 104.000 kWh/ano
Demanda caldera = 200.000 x 0,48 = 96.000 kWh/ano
Consumo EP hibrido = (104.000/2,40 x 1,954) + (96.000/0,86 x 1,190)
Consumo EP hibrido = 84.647 + 132.837 = 217.484 kWh/ano
Consumo EP solo caldera = 200.000/0,86 x 1,190 = 276.744 kWh/ano
Ahorro EP = 276.744 - 217.484 = 59.260 kWh/ano = 59,260 MWh/ano
CAE total = 59,260 MWh
Valoracion = 59,3 MWh x 100 EUR/MWh = 5.926 EUR

Errores comunes a evitar en la verificación ENAC

  • Bomba de calor no certificada para baja temperatura: debe poder funcionar hasta la temperatura de conmutacion establecida
  • Caldera infradimensionada: al asumir toda la carga en frio extremo, debe cubrir el 100% de la demanda punta
  • No considerar las heladas: el circuito de la bomba de calor inactiva debe estar protegido contra la congelacion
  • Ahorro sobreestimado: en zona E1, la menor cobertura BC limita el ahorro respecto a zonas templadas

Marco regulatorio aplicable

La ficha RES099 se rige por la Orden TED/845/2023 y el Real Decreto 36/2023. La zona E1 del CTE DB HE impone las condiciones climaticas mas severas. La bomba de calor instalada debe cumplir los requisitos del Reglamento (UE) 813/2013 para funcionamiento a baja temperatura, y la instalación global debe ajustarse al RITE.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)

Related resources

Start now

Create a file with datasheet RES099

14 days free. No card. No commitment.

Start now