TER172Tertiary

Parallel-mode hybridization - climate zone C1-C4

Hybridization of a combustion boiler with a heat pump in parallel mode in tertiary buildings located in climate zone C1-C4.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator TER172

Try the calculation without signing up. Results are not saved.

TER172Tertiary

Parallel-mode hybridization - climate zone C1-C4

Hybridization of a combustion boiler with a heat pump in parallel mode in tertiary buildings located in climate zone C1-C4.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building.
Boiler efficiency%Seasonal efficiency of the existing boiler.
Heat pump SCOP-Seasonal coefficient of performance of the heat pump.
Heat pump coverage%Percentage of demand covered by the heat pump.

Hibridacion modo paralelo en zona climatica C1-C4: continental moderado

La zona climatica C (subzonas C1, C2, C3 y C4) engloba ciudades como Barcelona, Granada, Cordoba, Badajoz y zonas del interior peninsular con un clima continental moderado. Los inviernos son mas frios que en las zonas costeras, con temperaturas que pueden descender regularmente por debajo de 0 grados en las noches mas frias, y la temporada de calefaccion se extiende durante 5 a 7 meses al ano.

La ficha TER172 adapta la hibridacion en modo paralelo a estas condiciones, donde la caldera de gas asume un papel mas importante que en zonas mediterraneas. La bomba de calor sigue siendo la fuente principal de calefaccion durante los periodos de temperaturas moderadas (octubre, noviembre, marzo, abril), pero la caldera interviene con mayor frecuencia durante los meses centrales del invierno.

En esta zona, el correcto dimensionamiento de la bomba de calor y la definicion de la estrategia de control son criticos para maximizar el ahorro. Un sistema bien diseñado puede cubrir entre el 55% y el 75% de la demanda anual con la bomba de calor.

Aspectos técnicos de la hibridacion paralelo en zona C

  • Temperaturas de diseño: La temperatura exterior de diseño en zona C se situa entre -2 y +2 grados, lo que requiere una bomba de calor dimensionada para operar en condiciones exigentes.
  • Degradacion del COP: A temperaturas exteriores bajas, el COP de la bomba de calor disminuye; en zona C, los ciclos de desescarche son mas frecuentes que en zonas costeras.
  • Horas de funcionamiento de caldera: Entre 500 y 1.000 horas anuales de apoyo, lo que incrementa el consumo de gas respecto a zonas A y B.
  • Gestion del punto de equilibrio: Se recomienda un punto de equilibrio entre 0 y 5 grados, optimizable según las tarifas energéticas locales.

Ejemplo de calculo para TER172 (zona C1-C4)

Hibridacion en un centro educativo en Granada (zona C3):

  • Demanda de calefaccion anual: 280.000 kWh
  • Cobertura bomba de calor: 65% (182.000 kWh)
  • Cobertura caldera gas: 35% (98.000 kWh)
  • SCOP bomba de calor: 3,6
  • Rendimiento caldera: 0,90
Consumo antes (solo caldera) = 280.000 / 0,90 = 311.111 kWh gas/ano

Consumo después:
  Bomba de calor = 182.000 / 3,6 = 50.556 kWh elec
  Caldera = 98.000 / 0,90 = 108.889 kWh gas

Ahorro gas = 311.111 - 108.889 = 202.222 kWh
Consumo electrico adicional = 50.556 kWh

Ahorro neto energía primaria:
  Gas evitado: 202.222 x 1,19 = 240.644 kWh
  Electrico consumido: 50.556 x 2,007 = 101.465 kWh
  Ahorro neto = 240.644 - 101.465 = 139.179 kWh = 139,18 MWh/ano

CAE total = 139,18 MWh

Valoracion = 139 MWh x 100 EUR/MWh = 13.918 EUR

Errores en verificación ENAC para TER172

  • No considerar los ciclos de desescarche: En zona C, el desescarche reduce significativamente el rendimiento efectivo de la bomba de calor; debe incluirse en el calculo del SCOP real.
  • Sobreestimar la cobertura de la bomba de calor: Los porcentajes de cobertura deben basarse en datos climaticos horarios de la localidad, no en estimaciones genericas.
  • No diferenciar las subzonas C1/C2/C3/C4: Aunque comparten ficha, las subzonas tienen diferencias significativas en severidad climatica.
  • No documentar la lógica de control: El sistema de gestión debe registrar cuando y por que se activa la caldera de apoyo.

Normativa para TER172

  • Orden TED/845/2023: Ficha TER172 para zona C1-C4.
  • Real Decreto 36/2023: Sistema CAE.
  • CTE DB-HE: Parametros climaticos de las subzonas C.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)