TER173Tertiary

Parallel-mode hybridization - climate zone D1-D3

Hybridization of a combustion boiler with a heat pump in parallel mode in tertiary buildings located in climate zone D1-D3.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator TER173

Try the calculation without signing up. Results are not saved.

TER173Tertiary

Parallel-mode hybridization - climate zone D1-D3

Hybridization of a combustion boiler with a heat pump in parallel mode in tertiary buildings located in climate zone D1-D3.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building.
Boiler efficiency%Seasonal efficiency of the existing boiler.
Heat pump SCOP-Seasonal coefficient of performance of the heat pump.
Heat pump coverage%Percentage of demand covered by the heat pump.

Hibridacion modo paralelo en zona climatica D1-D3: continental frio

La zona climatica D (subzonas D1, D2, D3) comprende ciudades como Madrid, Zaragoza, Valladolid, Burgos y gran parte del interior peninsular. Se caracteriza por inviernos frios con temperaturas mínimas que frecuentemente descienden por debajo de 0 grados durante semanas consecutivas, y veranos calurosos con demanda significativa de refrigeracion. La temporada de calefaccion puede extenderse de octubre a mayo, acumulando entre 1.500 y 2.500 grados dia.

La ficha TER173 esta diseñada para la hibridacion en modo paralelo en esta zona de alta severidad invernal. Aqui, la caldera de gas desempena un papel mucho mas relevante que en las zonas costeras, y la bomba de calor debe seleccionarse cuidadosamente para operar de forma eficiente a bajas temperaturas. Las bombas de calor con tecnología inverter y compresores de inyeccion de vapor (EVI) son especialmente recomendables en esta zona.

Aspectos técnicos de la hibridacion paralelo en zona D

  • Temperaturas exteriores criticas: La temperatura de diseño en zona D se situa entre -5 y -1 grados. La bomba de calor debe mantener capacidad de calefaccion a estas temperaturas.
  • Cobertura de la bomba de calor: Entre el 45% y el 65% de la demanda anual, dependiendo de la subzona y de la tecnología de la bomba.
  • SCOP reducido: El rendimiento estacional medio desciende respecto a zonas mas templadas, situandose tipicamente entre 2,8 y 3,8.
  • Desescarche intensivo: Los ciclos de desescarche son frecuentes y reducen la capacidad efectiva de la bomba de calor.
  • Estrategia de control avanzada: Es fundamental definir un punto de equilibrio (bivalencia) donde la caldera asume la carga principal, optimizando el coste energético global.

Ejemplo de calculo para TER173 (zona D1-D3)

Hibridacion en un edificio de oficinas en Madrid (zona D3):

  • Demanda de calefaccion anual: 400.000 kWh
  • Cobertura bomba de calor: 55% (220.000 kWh)
  • Cobertura caldera gas: 45% (180.000 kWh)
  • SCOP bomba de calor: 3,2
  • Rendimiento caldera: 0,90
Consumo antes (solo caldera) = 400.000 / 0,90 = 444.444 kWh gas/ano

Consumo después:
  Bomba de calor = 220.000 / 3,2 = 68.750 kWh elec
  Caldera = 180.000 / 0,90 = 200.000 kWh gas

Ahorro gas = 444.444 - 200.000 = 244.444 kWh
Consumo electrico adicional = 68.750 kWh

Ahorro neto energía primaria:
  Gas evitado: 244.444 x 1,19 = 290.889 kWh
  Electrico consumido: 68.750 x 2,007 = 137.981 kWh
  Ahorro neto = 290.889 - 137.981 = 152.908 kWh = 152,91 MWh/ano

CAE total = 152,91 MWh

Valoracion = 153 MWh x 100 EUR/MWh = 15.291 EUR

Errores en verificación ENAC para TER173

  • No seleccionar bomba de calor apta para bajas temperaturas: En zona D, la bomba debe mantener capacidad a -7 grados como mínimo; usar equipos diseñados para climas suaves genera un ahorro real inferior al calculado.
  • Subestimar la contribucion de la caldera: Asignar un porcentaje demasiado alto a la bomba de calor en zona D produce calculos irrealistas.
  • No monitorizar el punto de bivalencia real: El sistema debe registrar la temperatura a la que efectivamente se activa la caldera para validar los calculos.
  • Omitir el consumo electrico de resistencias auxiliares de desescarche: Este consumo adicional debe restarse del ahorro.

Normativa para TER173

  • Orden TED/845/2023: Ficha TER173 con parametros para zona D1-D3.
  • Real Decreto 36/2023: Sistema CAE.
  • CTE DB-HE: Parametros climaticos de zona D.
  • EN 14825: Rendimiento estacional a diferentes temperaturas.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)