TER176Tertiary

Hybridization in alternative mode - climatic zone B3 or B4

Hybridization of a combustion boiler with a heat pump in alternative mode in tertiary buildings located in climatic zone B3 or B4.

Compliant with Orden TED/845/2023 · MITECO datasheet catalogue

Calculator TER176

Try the calculation without signing up. Results are not saved.

TER176Tertiary

Hybridization in alternative mode - climatic zone B3 or B4

Hybridization of a combustion boiler with a heat pump in alternative mode in tertiary buildings located in climatic zone B3 or B4.

Calculate automatically with intelligent technology

Upload the technical sheets, invoices or certificates of the equipment before and after the action. The parameters will be filled in automatically.

Limit: 0 / 10 documents (split between BEFORE and AFTER)

BEFORE the action

Existing equipment

Drag or click to upload

PDF, image, Word or Excel

AFTER the action

New equipment

Drag or click to upload

PDF, image, Word or Excel

Calculation parameters

Want to save this calculation and create a file? Create your free account

Calculation parameters

ParameterUnitDescription
Heating demandkWh/anoAnnual heating demand of the building.
Boiler efficiency%Seasonal efficiency of the existing boiler.
Heat pump SCOP-Seasonal coefficient of performance of the heat pump.
Heat pump coverage%Percentage of demand covered by the heat pump.

Hibridacion modo alternativo en zona climatica B3/B4: conmutacion eficiente en clima moderado

La ficha TER176 regula la hibridacion en modo alternativo para edificios terciarios en la zona climatica B3/B4, que incluye ciudades como Valencia, Sevilla, Alicante, Cordoba y Murcia. En esta zona de clima mediterraneo moderado, la bomba de calor opera como fuente única de calefaccion durante la mayor parte del invierno, conmutando a caldera de gas solo cuando las temperaturas descienden por debajo del punto de corte establecido.

La zona B3/B4 presenta inviernos suaves pero con episodios puntuales de frio que justifican mantener la caldera como respaldo. La temperatura mínima de calculo se situa entre 0 y 5 grados, y las heladas son infrecuentes pero no excepcionales. Esta condicion hace que el modo alternativo sea una estrategia óptima: la simplificacion del control (un solo generador activo a la vez) no sacrifica eficiencia significativa respecto al modo paralelo.

Aspectos técnicos de la hibridacion alternativa en B3/B4

  • Temperatura de conmutacion recomendada: Entre 3 y 6 grados, dependiendo de las prestaciones de la bomba de calor a baja temperatura.
  • Horas de operación de caldera: Entre 150 y 400 horas anuales, frente a las menos de 100 horas en zona A3/A4.
  • Cobertura de la bomba de calor: Entre el 72% y el 88% de la demanda anual de calefaccion.
  • Ventaja del modo alternativo en B3/B4: La ausencia de operación simultanea simplifica el control y evita problemas de compatibilidad hidraulica entre caldera y bomba de calor.

Ejemplo de calculo para TER176 (zona B3/B4)

Hibridacion alternativa en un centro comercial en Sevilla (zona B4):

  • Demanda de calefaccion anual: 160.000 kWh
  • Cobertura bomba de calor: 80% (128.000 kWh)
  • Cobertura caldera: 20% (32.000 kWh)
  • SCOP bomba de calor: 4,3
  • Rendimiento caldera: 0,90
Consumo antes (solo caldera) = 160.000 / 0,90 = 177.778 kWh gas/ano

Consumo después:
  Bomba de calor = 128.000 / 4,3 = 29.767 kWh elec
  Caldera = 32.000 / 0,90 = 35.556 kWh gas

Ahorro gas = 177.778 - 35.556 = 142.222 kWh
Consumo electrico adicional = 29.767 kWh

Ahorro neto energía primaria:
  Gas evitado: 142.222 x 1,19 = 169.244 kWh
  Electrico consumido: 29.767 x 2,007 = 59.742 kWh
  Ahorro neto = 169.244 - 59.742 = 109.502 kWh = 109,50 MWh/ano

CAE total = 109,50 MWh

Valoracion = 110 MWh x 100 EUR/MWh = 10.950 EUR

Errores en verificación ENAC para TER176

  • No documentar la lógica de conmutacion: El verificador ENAC exigira evidencia del algoritmo de control que determina cuando se conmuta entre generadores.
  • Transitorias no contabilizadas: Al cambiar de caldera a bomba de calor, el sistema necesita tiempo para estabilizarse; este periodo reduce ligeramente el ahorro efectivo.
  • Usar datos climaticos de subzona incorrecta: B3 y B4 tienen perfiles termicos diferentes; B4 tiene veranos mas calurosos.
  • No considerar la contribucion de la refrigeracion: Si la bomba de calor es reversible, la refrigeracion debe analizarse por separado.

Normativa para TER176

  • Orden TED/845/2023: Ficha TER176 modo alternativo zona B3/B4.
  • Real Decreto 36/2023: Sistema CAE.
  • CTE DB-HE: Zona climatica B3/B4.

Required documents

  • D1Reference-situation documentation (existing equipment)
  • D2Technical documentation of the new equipment (datasheet, certificates)
  • D3Invoice or contract for the action
  • D4Before/after photographic report
  • D5Supporting savings calculation (generated automatically)

Related resources

Start now

Create a file with datasheet TER176

14 days free. No card. No commitment.

Start now